💨 Airside Rules

RuleValue / RangeNotes
Supply duct velocity — main trunk600–1,200 FPMSMACNA; max 1,500 FPM
Supply duct velocity — branch400–800 FPMNC-35 spaces
Return duct velocity400–700 FPMLower than supply to reduce noise
Duct friction loss target0.08–0.10 in/100ftEqual friction sizing method
CFM/ton cooling350–450 CFM/tonStandard DX and CHW coils
Supply air temp (cooling)55–60°FTypical LAT from cooling coil
Supply air temp (heating)90–120°FHot water coil or gas heat
OA fraction — minimum10–20%ASHRAE 62.1 minimum ventilation
Filter face velocity300–500 FPMHigher → shorter filter life
Sensible heat factor (sea level)1.08Q = 1.08 × CFM × ΔT (BTU/hr)
Latent heat factor (sea level)0.68Q = 0.68 × CFM × ΔW_gr (BTU/hr)

💧 Hydronic Rules

RuleValue / RangeNotes
CHW ΔT (supply–return)10–12°FTypical; 14–16°F for high-ΔT plants
HHW ΔT (supply–return)20–40°FHigher ΔT = smaller pipe + lower pump energy
CHW GPM/ton2.0–2.4 GPM/tonAt 10°F ΔT; 1.5 GPM/ton at 16°F ΔT
Pipe friction target1–4 ft/100ftDarcy-Weisbach design range
Pipe velocity — mains4–8 ft/sASHRAE recommended
Pipe velocity — pump suction≤3 ft/sPrevent cavitation
Hydronic factor (water)500Q = 500 × GPM × ΔT (BTU/hr)
Pump efficiency (typical)65–80%Centrifugal at BEP; VFD reduces at part load

🌡️ Psychrometric & Load Rules

RuleValue / RangeNotes
Comfort RH range30–60%ASHRAE 55; 40–50% ideal
Comfort DB range (cooling)73–79°FASHRAE 55 operative temp
Cooling load — office200–350 ft²/tonRule-of-thumb; varies widely
Lighting load density0.5–2.0 W/ft²LED office; older T8 ~1.5–2.5 W/ft²
People load (sensible)250–300 BTU/hr/personOffice activity; 750 BTU/hr total
Latent load fraction — humid climate20–35%Of total cooling load
SHR — typical commercial coil0.70–0.80DX and CHW in mixed climate
Enthalpy — summer outdoor (SE US)36–42 BTU/lb95°F / 75°F WB typical design

🔧 Equipment Rules

RuleValue / RangeNotes
Chiller COP (centrifugal)5.0–7.00.5–0.7 kW/ton; ASHRAE 90.1 minimums
DX system COP3.0–4.5Packaged rooftop; varies by SEER
Boiler efficiency (condensing)90–98%Modulating; needs low return temp
Cooling tower approach5–10°FLeaving CW vs ambient WB
Fan motor sizingBHP × 1.15–1.25Motor selection oversizing factor
VFD savings at 80% speed~49% energy reductionAffinity law: power ∝ speed³
Pump motor sizingWHP / pump eff × 1.15Safety factor on top of efficiency

ℹ️ About This Reference

This page collects the rules of thumb HVAC engineers reach for every day — duct and pipe velocity limits, chilled- and hot-water delta-T, load densities, equipment efficiencies, and the sensible and latent heat factors — into four sorted reference tables. It is a bookmark-and-go cheat sheet, not a calculator with inputs.

Rules of thumb are for fast estimating and for checking whether a detailed result is believable. They are deliberately broad, and the right value for a specific project depends on climate, building type, and code. Always confirm with a real calculation before committing a number to a drawing.

🔬 Key Constants & Method

Sensible heat (air)Q (BTU/hr) = 1.08 × CFM × ΔT (°F), sea level
Latent heat (air)Q (BTU/hr) = 0.68 × CFM × ΔW (gr/lb), sea level
Hydronic heat (water)Q (BTU/hr) = 500 × GPM × ΔT (°F)
Cooling capacity1 ton = 12,000 BTU/hr = 3.517 kW
VFD affinity lawpower ∝ speed³  →  80% speed ≈ 51% power

The air factors 1.08 = 60 × 0.075 × 0.24 and 0.68, and the water factor 500 ≈ 60 × 8.33 × 1.0, follow standard ASHRAE Fundamentals unit relations and are sea-level air-density values that fall at altitude. The affinity-law cube relationship comes from fan and pump similarity laws. Velocity, ΔT, and efficiency ranges are common SMACNA / ASHRAE design practice, shown as ranges because real projects vary.

❓ Frequently Asked Questions

What is the sensible heat factor of 1.08?
The factor 1.08 lets you find sensible heat from airflow and temperature difference: Q (BTU/hr) = 1.08 times CFM times delta-T in degrees F. It equals 60 minutes per hour times 0.075 lb per cubic foot of standard air times 0.24 BTU per lb per degree F. Because it depends on air density, 1.08 is a sea-level value and decreases at higher altitude as the air thins.
What is the 500 factor for hydronic loads?
For water, Q (BTU/hr) = 500 times GPM times delta-T in degrees F. The 500 comes from 60 minutes per hour times 8.33 lb per gallon times 1.0 BTU per lb per degree F for water, which rounds to about 500. It is the hydronic counterpart to the 1.08 air factor and is used constantly for coil, chiller, and boiler flow checks.
How much energy does a VFD save at 80 percent speed?
Roughly 49 percent. Fan and pump power follows the affinity law, varying with the cube of speed, so 0.8 cubed is about 0.51, meaning the motor draws around 51 percent of full power and saves about 49 percent. This cubic relationship is why small speed reductions on variable-flow systems produce large energy savings.
Are these rules of thumb a substitute for real calculations?
No. These values are for quick estimating, checking another engineer's work, and catching gross errors. Final design requires proper load calculations, duct and pipe sizing, and equipment selection to the applicable codes and ASHRAE standards. The ranges shown are representative and vary with climate, building type, and project requirements.

🔗 Related Tools

Design Sanity Checker Velocity Calculator CFM / Tons / BTU Converter HVAC Unit Conversions
Free 14-Day Trial  ·  No Credit Card

Do the full calculation in AIM Works

This calculator handles one step. AIM Works runs the complete MEP design workflow — thermal load calculations, duct & pipe networks, equipment selection, code compliance, and an AI design assistant — in one tool.

  • ✓  ASHRAE 62.1 ventilation + CLTD/CLF/RTS load methods
  • ✓  Darcy-Weisbach pipe & duct network solvers
  • ✓  ASHRAE 90.1 / IMC / NFPA compliance checks
  • ✓  20 free AI design messages included in trial
Try It Free for 14 Days →
No credit card  ·  Cancel anytime
See plans & pricing →