Cooling coil leaving-air conditions from entering air, capacity, and SHR, with apparatus dew point.
Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.
Book a Demo →This coil leaving air calculator predicts the dry-bulb temperature and humidity of air leaving a cooling coil from the entering condition, airflow, total capacity in tons, and sensible heat ratio. It also splits the load into sensible and latent tons, reports the temperature drop, leaving enthalpy, RH, and wet bulb, finds the apparatus dew point and bypass factor, and is altitude-corrected for the lower air density at elevation.
Leaving air conditions set the supply temperature your diffusers deliver and the moisture the coil removes, so they drive both comfort and dehumidification. The tool flags leaving temperatures low enough to risk coil frost and high enough to suggest the coil or airflow is mismatched, helping you sanity-check a selection before specifying equipment.
| Load split | Qsens = tons × 12000 × SHR, Qlat = tons × 12000 × (1 − SHR) |
| Air mass flow | ṁ = 60 · CFM ÷ vin, vin = 0.370486 · (EAT + 459.67) · (1 + 1.607858 · Win) ÷ P |
| Sensible ΔT | ΔT = Qsens ÷ [ṁ · (0.240 + 0.444 · Win)], LAT = EAT − ΔT |
| Latent ΔW | ΔW = Qlat ÷ [ṁ · (1061 + 0.444 · LAT)] [lb/lb] |
| Pressure | P = 14.696 · (1 − 6.8754×10−6 · Z)5.2559 psia, Z = elevation (ft) |
Total capacity is split by SHR. The airflow is treated as actual CFM at the entering condition and converted to a dry-air mass flow; the sensible part sets the temperature drop and the latent part the humidity-ratio drop, so the leaving enthalpy is exactly hin − Qtotal ÷ ṁ. At standard air (v = 13.33 ft³/lb, W ≈ 0) the sensible relation reduces to the familiar Qsens = 1.08 · CFM · ΔT; using the real entering density keeps the result consistent with the AIM Works cooling coil calculator and correct at altitude. Humidity ratio, enthalpy, RH, and wet bulb use the ASHRAE Handbook—Fundamentals (2021) Chapter 1 moist-air equations at the barometric pressure for your elevation. The apparatus dew point (ADP) is where the entering-to-leaving process line, extended, meets the saturation curve, and the bypass factor is (LAT − ADP) ÷ (EAT − ADP). A leaving state above 100 % RH, or a line with no ADP, cannot be produced by a cooling coil and is flagged rather than reported as normal. This checks a selection; it is not a coil rating, so confirm with the manufacturer’s selection software.
AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.
Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.