Humidity ratio, dew point, and vapor pressure from dry bulb, RH, and elevation.
| Condition | DB (°F) | RH (%) | W (gr/lb, sea level) |
|---|---|---|---|
| Typical indoor design — summer | 75 | 50 | 64.6 |
| Typical indoor design — winter | 70 | 30 | 32.5 |
| Cooling coil leaving air | 55 | 90–95 | 57.8–61.1 |
| Hot-humid outdoor (Gulf Coast type) | 91 | 60 | 132.1 |
| Hot-dry outdoor (desert) | 108 | 13 | 46.9 |
| Cold outdoor (northern US winter) | -16 | 80 | 1.8 |
| ASHRAE 55 upper humidity limit | — | — | 84.0 (W = 0.012) |
Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.
Book a Demo →This humidity ratio calculator converts dry-bulb temperature and relative humidity into the moisture content of the air, expressed as humidity ratio in grains per pound, pounds per pound, and grams per kilogram. It also returns dew point, specific humidity, water-vapor partial pressure, and a typical comfort-band check, corrected for your site elevation.
Humidity ratio is the absolute moisture measure engineers track through a system, because it stays fixed during sensible heating and cooling and only changes when moisture is added or removed. That makes it the right variable for coil latent load, dehumidification, and verifying outdoor-air moisture against indoor design targets.
| Saturation pressure | Pws: Hyland–Wexler equations (over ice below 32 °F, over liquid water above) |
| Humidity ratio | W = 0.621945 · Pw ÷ (P − Pw), Pw = RH · Pws, P = 14.696 · (1 − 6.8754×10−6 · Z)5.2559 psia |
| Grains per pound | Wgr = W × 7000 |
| Specific humidity | q = W ÷ (1 + W) |
| Dew point | Pws(Tdp) = Pw, solved numerically (frost point below 32 °F) |
These are the ASHRAE Handbook—Fundamentals (2021) Chapter 1 moist-air equations in IP units — the same set as the AIM Works psychrometric calculator, so the same state reads the same on every page. Barometric pressure P comes from your elevation through the standard atmosphere (14.696 psia at sea level): at a fixed dry bulb and RH, humidity ratio rises as pressure falls. Grains per pound multiply W by 7000, g/kg by 1000, and specific humidity is W ÷ (1 + W). The comfort check is a rule of thumb (30–60 % RH at 68–76 °F) plus the ASHRAE Standard 55 upper limit W ≤ 0.012; it is not a full Standard 55 thermal-comfort analysis.
AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.
Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.