DOAS Sizing Calculator

Dedicated outdoor air system sizing: outdoor airflow, coil capacity, and energy recovery.

Space & Occupancy
Design Conditions
DOAS Sizing Results
Total OA (Vot)
—
standard CFM
Design Occupants
—
people
Cooling Coil — Total
—
tons, with selected recovery
Cooling Coil — Sensible
—
tons, with selected recovery
Heating Coil
—
MBH, with selected recovery
Recovery Cooling Saved
—
tons
System Summary
ParameterNo RecoveryWith Selected RecoveryUnit
Inputs, results, and method — as an Excel workbook or plain CSV.

Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.

Book a Demo →
About This Calculator

This DOAS sizing calculator estimates a dedicated outdoor air system from occupancy and design conditions. Enter the floor area, space type (ASHRAE 62.1 Table 6-1 rates and default density), Ez, summer and winter outdoor conditions, site elevation, supply temperature and leaving dew point, return air conditions, and the energy recovery device; the tool returns the outdoor air CFM, design occupants, total and sensible cooling coil capacity, heating coil MBH, and the cooling tons energy recovery saves.

A DOAS conditions ventilation air separately from space sensible cooling, which improves humidity control and pairs well with fan coils, VRF, chilled beams, or radiant systems. The summary table contrasts the system with and without energy recovery so the value of an ERV is clear.

Formula & Method
QuantityEquation
Outdoor air (62.1)Vbz = Rp · Pz + Ra · Az;  Pz = D · Area ÷ density;  Vot = Vbz ÷ Ez
Outdoor humidityW from DB/WB at site pressure (ASHRAE Fundamentals Ch. 1, Eq. 33; Hyland–Wexler saturation)
Recovery-conditioned airT = T‑OA − εs(T‑OA − T‑RA);  W = W‑OA − εL(W‑OA − W‑RA)
Total coil loadBTU/hr = 4.5 × CFM × (h‑entering − h‑leaving)
Sensible coil loadBTU/hr = 1.08 × CFM × (T‑entering − T‑supply)
Heating coilBTU/hr = 1.08 × CFM × (T‑supply − T‑entering)

Outdoor air follows the ASHRAE 62.1-2019 zone calculation (Table 6-1 rates; Vbz = Rp·Pz + Ra·Az, Voz = Vbz ÷ Ez). For a 100% outdoor air system the intake is the sum of the zone Voz values; the occupant diversity D belongs to the multiple-zone recirculating equation, so leave it at 100% unless you are deliberately applying 62.1’s short-term averaging. Table 6-1 rates are based on standard air (0.075 lb/ft³); the table permits, but does not require, adjusting for actual density, and holding the mass flow is the conservative reading. So the OA here is standard CFM and the coil loads use the standard-air factors 4.5 (= 60 × 0.075) and 1.08 (= 60 × 0.075 × 0.24) without altitude scaling; site elevation changes the psychrometric state (humidity ratio from wet bulb and dew point at local pressure) and the actual CFM the fan moves. The coil dehumidifies to the dew point you enter (never adding moisture). A wet coil leaves air at about 90% RH, roughly the dew point + 3 °F, so when the supply dry-bulb is warmer than that — a neutral-air DOAS — the coil load is taken to dew point + 3 °F and the summer reheat back up to the supply dry-bulb is reported separately. Moist-air enthalpy is h = 0.240·T + W·(1061 + 0.444·T). Energy recovery assumes balanced supply and exhaust flow at the entered return conditions; the ERV options apply one effectiveness to both temperature and humidity (εs = εL), the HRV transfers sensible heat only, and in summer recovery is bypassed when it would add load (outdoor enthalpy below return for an ERV, outdoor dry-bulb below return for an HRV). Use the manufacturer’s AHRI 1060 sensible and latent ratings for a selection. If the wheel can be stopped or bypassed for frost control, size the heating coil for the no-recovery value shown in the summary.

Frequently Asked Questions
What is a DOAS and when is it used?
A dedicated outdoor air system (DOAS) conditions only the ventilation air, delivering it neutral or cool while a separate system handles the space sensible load. Decoupling ventilation from sensible cooling improves humidity control and lets the main system be smaller. DOAS is common with fan coils, VRF, chilled beams, and radiant systems, especially where latent control matters.
How is the total outdoor air CFM determined?
The tool uses the ASHRAE 62.1 breathing-zone form Vbz = Rp times people plus Ra times area, then divides by the zone air distribution effectiveness Ez. Occupants are the floor area divided by the occupant density (default densities from 62.1 Table 6-1), times an optional diversity factor that defaults to 100 percent, because a 100 percent outdoor air system sums the zone requirements without diversity. The result is in standard CFM; the summary also shows the actual airflow at the site elevation for fan selection.
How is the DOAS cooling coil load calculated?
Total coil load is an enthalpy calculation: 4.5 times outdoor air CFM times the enthalpy difference between the air entering the coil (outdoor air, or air leaving the energy recovery device) and the supply condition, set by the supply dry-bulb and the leaving dew point you enter. 4.5 equals 60 times the standard air density of 0.075. The sensible portion uses 1.08 times CFM times the dry-bulb difference, and the latent portion is the rest. Because a DOAS conditions full outdoor air, the latent share is usually large, which is why enthalpy is used.
How much does energy recovery reduce the coil size?
An energy recovery ventilator pre-conditions incoming outdoor air using exhaust air, cutting both temperature and humidity extremes. At 65 to 80 percent effectiveness it can substantially shrink the cooling coil, and the heating coil too unless frost control stops or bypasses the wheel. This tool compares coil capacity with and without recovery, assuming balanced flows and equal sensible and latent effectiveness for the ERV options (sensible only for the HRV option), and reports the cooling tons saved.
Related Tools
Ventilation Calculator OA / RA % Calculator Mixed Air Temp ACH Calculator Enthalpy Calculator
AIM Works · launches Oct 15, 2026

Connect the calculation to the rest of the project.

AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.

  • Peak loads (RTS or CLTD/CLF) and ASHRAE 62.1-2019 ventilation
  • Equipment and plant sizing against ASHRAE 90.1-2022 efficiency floors
  • Design Review that cites the check behind every finding
  • An AI co-pilot that drafts changes — you approve each one
Book a Demo →
A walkthrough first, then a 14-day free trial. No credit card.
How the calculations work →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.