🌍 Air Stream Inputs

Design outdoor dry-bulb
Space / return dry-bulb
Ventilation + economizer OA
Recirculated return airflow
From psychrometric chart or weather data
Space humidity ratio target

📚 OA% Reference Guide

OA% System Type / Condition Notes Mode
10–15% Minimum ventilation only ASHRAE 62.1 minimum; cooling season Mixed
15–30% Typical commercial VAV Standard summer / winter design Mixed
30–70% Partial economizer OA cooler than RA; free cooling assist Econ
70–100% Full / near-full economizer OA at or below setpoint; compressor off Econ
100% 100% OA systems (labs, OR) No recirculation; DOAS / critical spaces 100% OA
Run this for your whole project — free →
Start a free 14-day trial. No credit card.

📝 About This Calculator

This mixed air temperature calculator blends outdoor and return air streams into the conditions entering a cooling or heating coil. Enter the temperature, airflow, and humidity ratio of each stream, and the tool returns the mixed dry-bulb temperature, the outdoor air fraction, the mixed humidity ratio, and the mixed enthalpy, with a flow diagram and an economizer check.

Mixed air conditions set the entering state for coil sizing and tell you whether free cooling is available or whether preheat is required. By mixing on enthalpy as well as temperature, the tool supports both temperature and enthalpy economizer logic.

🔢 Formula & Method

QuantityEquation
OA fractionOA‑frac = OA CFM ÷ (OA CFM + RA CFM)
Mixed tempMAT = OA‑frac · T‑OA + RA‑frac · T‑RA
Mixed humidityW‑mix = OA‑frac · W‑OA + RA‑frac · W‑RA
Enthalpyh = 0.240 · T + (W ÷ 7000) · (1061 + 0.444 · T)

Mixed conditions are the flow-weighted (adiabatic mixing) average of the two streams, the standard relationship in ASHRAE Fundamentals. The enthalpy equation h = 0.240·T + W·(1061 + 0.444·T) uses temperature in °F and humidity ratio W in lb/lb dry air, where the tool divides the grains-per-pound input by 7,000. Comparing outdoor and return enthalpy is the basis of an enthalpy economizer.

❓ Frequently Asked Questions

How is mixed air temperature calculated?
Mixed air temperature is the flow-weighted average of the outdoor and return air streams: MAT = OA fraction times outdoor temp plus return fraction times return temp, where each fraction is that stream's CFM divided by the total. For example, 500 CFM of 95 degree F outdoor air mixed with 2,000 CFM of 75 degree F return air gives a mixed temperature of about 79 degrees F.
Why also mix on enthalpy and humidity ratio?
Temperature alone misses the moisture content, which matters for cooling coil load and economizer decisions. This tool mass-weights the outdoor and return humidity ratios and enthalpies the same way it does temperature. Comparing outdoor and return enthalpy, not just dry-bulb, is the basis of an enthalpy economizer, which avoids bringing in cool but very humid outdoor air.
When does mixed air need a preheat coil?
In cold weather with significant outdoor air, the mixed air temperature can fall low enough to risk coil freezing or to sit below the desired coil entering temperature. When the mixed temperature drops toward or below about 45 degrees F, a preheat coil or a reduction in outdoor air is typically needed. This tool warns when the calculated mixed temperature is in that range.
What enthalpy formula does this tool use?
It uses the standard moist-air enthalpy relation h = 0.240 times T plus W times (1061 + 0.444 times T), with temperature T in degrees F and humidity ratio W in pounds of moisture per pound of dry air (the tool converts the grains-per-pound input by dividing by 7,000). This is the psychrometric enthalpy equation from ASHRAE Fundamentals, applied to each stream and then mass-weighted for the mixture.

🔗 Related Tools

OA / RA % Calculator Enthalpy Calculator Supply Air Temp Ventilation Calculator DOAS Sizing
Free 14-Day Trial  ·  No Credit Card

Do the full calculation in AIM Works

This calculator handles one step. AIM Works runs the complete MEP design workflow — thermal load calculations, duct & pipe networks, equipment selection, code compliance, and an AI design assistant — in one tool.

  • ✓  ASHRAE 62.1 ventilation + CLTD/CLF/RTS load methods
  • ✓  Darcy-Weisbach pipe & duct network solvers
  • ✓  ASHRAE 90.1 / IMC / NFPA advisory compliance checks
  • ✓  20 free AI design messages included in trial
Try It Free for 14 Days →
No credit card  ·  Cancel anytime
See plans & pricing →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.